This Inbal Valve
combines a deluge and a pressure control function in
the same valve. The requirement for pressure control
is typically associated with a large system where the
fire pump is designed for the capacity of several deluge
systems. When only part of the deluge system is operated,
the delivery pressure to each system should be reduced
to meet the components' pressure rating and to prevent
flooding by use of excess flow. When several deluge
systems operate simultaneously, the pressure control
deluge valves ensure balancing of the water pressure
resources and efficient use of the overall capacity.
|